MGM Evaluates Its Lamp Options for New Office Space

For 755 troffers in a new IT office space, MGM Resorts evaluated three lamp options:

■   A code–mandated minimum of 2×4 linear, 30,000-hour fluorescent T8 lamps (96 watts)
■   Extended-life, 75,000-hour, 2×4 linear fluorescent T8 lamps (84 watts)
■   2×2 LED, 50,000-hour lamp fixtures (44 watts)

Both fluorescent options assumed three lamps per fixture, while the LED option had one module.

Each lamp option was evaluated with and without controls. The additional installation cost for controls with each lamp option was roughly $47. The analysis assumed that occupancy controls would decrease consumption for the two fluorescent lamp options by 30%. For the LED option, a roughly 42% usage decrease for controls was projected due to dimming and daylight dimming capabilities as well as occupancy sensors.

The 10-year cost of ownership was projected for each system (see table below). For the 30,000-hour fluorescent option, the projection included the cost of one lamp replacement.

MGM ultimately chose the LED upgrade with full dimming controls. The breakdown of cost and benefits over the baseline option included:

■   $165,000 lighting spend ($69,000 incremental)
■   68% energy reduction totaling 125,000 kWh saved annually
■   33.9% ROI

Advertisements

Leave a Reply

Fill in your details below or click an icon to log in:

WordPress.com Logo

You are commenting using your WordPress.com account. Log Out / Change )

Twitter picture

You are commenting using your Twitter account. Log Out / Change )

Facebook photo

You are commenting using your Facebook account. Log Out / Change )

Google+ photo

You are commenting using your Google+ account. Log Out / Change )

Connecting to %s